Pemutus Litar Vakum(VCB)12KV 24KV 36KV BKZF-12 LBS vakum pengeluaran
BKZF(R)-12 Jenis pengeluaran Voltan Sederhana
Jenis: Penyentuh AC
Spesifikasi:
Parameter teknikal utama:
TIDAK. | Parameter | Unit | Nilai | ||||||
BKZC(R)-12-630/400/250 | BKZC(R)-12-630/400/250 | ||||||||
1 | Voltan Ternilai | kV | 7.2 | 12 | |||||
2 | Nilai Semasa | A | 630 | 400 | 250 | 630 | 400 | 250 | |
3 | Nilai semasa penutupan (rms) | A | 6300 | 4000 | 2500 | 6300 | 4000 | 2500 | |
4 | arus pecah terkadar | 5040 | 3200 | 2500 | 5040 | 3200 | 2500 | ||
5 | Arus haba 4S | 6300 | 4000 | 2500 | 6300 | 4000 | 2500 | ||
6 | Hadkan arus pecah | 6300 | 4000 | 2500 | 6300 | 4000 | 2500 | ||
7 | Kekerapan kuasa menahan voltan | kV | 32 | 42 | |||||
8 | kekerapan operasi | Masa/j | 300 | ||||||
9 | Masa hayat elektrik | AC-3 | ×104Masa | 25 | |||||
AC-4 | 10 | ||||||||
10 | Kehidupan mekanikal | 30 | |||||||
11 | Voltan operasi berkadar | V | AC110/220 | ||||||
12 | Arus tarik gegelung penutup | A | ≤ DC6/3 | ||||||
13 | Memegang gegelung memegang arus | D:DC0.32/0.16 | |||||||
14 | Arus gegelung trip Shunt | J:DC2.5/1.3 |
TIDAK. | Parameter | Unit | Nilai | |
BKZC(R)-12-630/400/250 | BKZC(R)-12-630/400/250 | |||
1 | jarak sentuhan | mm | 4.5+1.0/-0.5 | 6+1.0-0.5 |
2 | hubungi overtravel | 1.5±0.5 | ||
3 | Purata kelajuan penutupan | m/s | 0.1~0.25 | |
4 | Purata kelajuan pembukaan | 0.3~0.6 |