Inquiry
Form loading...
Products Categories
Featured Products

Disconnector 12KV 24KV 36KV GW4 outdoor disconnectors

GW4-12 outdoor type series disconnectors

GW4 series disconnectors shall be applied to switching of the HV transmission equipment with rated frequency 50Hz or 60Hz when no load is applied to the HV power supply line and electric isolation of the HV electric equipments, such as the HV bus, the breaker, etc. to be overhauled from the charged HV circuit.

    1jus

    Product Description

    GW4 series disconnectors shall be applied to switching of the HV transmission equipment with rated frequency 50Hz or 60Hz when no load is applied to the HV power supply line and electric isolation of the HV electric equipments, such as the HV bus, the breaker, etc. to be overhauled from the charged HV circuit.

    This series of disconnector is the double-column horizontal rotating central single-break type disconnector and is composed of the base, the supporting insulator and the conductive part; and the earthing switches can be added on one side or two sides. Moreover, the main switch and the earthing switch can be applied to three-phase linked operation and split-phase operations by using the electric mechanism or the manual mechanism.

    The vertical transmission rod shall drive one supporting insulator of the disconnector to rotate when the operating mechanism of the main switch runs; and the other supporting insulator shall be driven to rotate by using one set of intersected four-bar linkage structure in the base; therefore, opening and closing of the left conductive part and the right conductive part can be realized.

    Product feature

    1.Complete in specifications,high technical parameters is high, wide range. Additional, wide scope of application , it can be used for high layout. Installation way is flexible. 

    2.Perfect sealing Performance and Resistant To Rust 

    3.Simple, reliable mechanical rotating way. 

    4.Perfect dustproof, waterproof, and anti-corrosion ability. 

    5.Full set of steel galvanized foundation frame and the vertical and horizontal dwang for option.

    Service Conditions:

    ? Altitude:1000m~3000m

    ?Ambient temperature:-30°C ~-40°C

    ?Wind pressure:≤700pa(wind speed 34m/s)

    ?Earthquake intensity:≤8 degree

    ?Rative humidity of air:monthly≤90°C,daily≤95°C

    ?Environment degree: degree III

    ?Cannot be use on the condition of the danger of fire and blast,heavy pollution,chemical etching,strong shake ect.

    Technical parameter

    Rated voltage kV

    40.5

    72.5

    126

    Rated current A

    1250, 2000, 2500, 3150

     

    Rated peak withstand current kA

    Disconnector

    100, 125

     

    Earthing switch

    100, 125

     

    Rated short-time withstand current and duration kA/s

    Disconnector

    40/3, 50/3

     

    Earthing switch

    40/3, 50/3

    Rated short-time power frequency withstand voltage (rms.) kV

    To earth

    95

    140

    230

     

    Between breaks

    118

    160

    265

    Rated lightning impulse withstand voltage (peak) kV

    To earth

    185

    325

    550

     

    Between breaks

    215

    375

    630

     

    Rated values of the bus- tranfer current switching capability of disconnectors

    Opening/closing current A

    80%Ir(≤ 1600)

     

    Conversion voltage V

    100

     

    Times of opening/ closing

    100

    Small capacitive current during opening and closing A

    1

    Small inductive current during opening and closing A

    0.5

    Radio interference level μV

    --

    --

    ≤ 2500

     

     

    Rated static mechanical load of the terminal N

    Horizontal longitudinal direction

    1000

    1000,1250

     

    Horizontal transverse direction

    750

    750